DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package

Basic Info

Model No.:  DV-5 Red-E

Product Description

Model NO.: DV-5 Red-E Type: Portable Fire Extinguisher Size: 4kg Portable Extinguisher: Portable Dry Powder Fire Extinguisher Retirement Life: 10 Years Power Source: Chemical Reaction Fire Extinguisher Color: Bright Red Trademark: Tyco Specification: 1-1/2 thru 8 Inch (DN40 thru DN200) Agent: Dry Powder Object: ABC Certification: UL Effective Range: 9m Dry Powder Type: Ordinary Dry Powder Working Pressure: 20 to 250 Psi (1,4 to 17,2 Bar) Body Material: Gauge Steel Transport Package: as Customer Require Origin: Netherlands DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package


General     Description

The TYCO DV- 5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed within a free-stand-ing cabinet designed to occupy minimal floor space and to provide an aestheti-cally pleasing enclosure for a fire pro-tection valve riser. The entire package is pre- wired and the water inlet and outlets to the valve riser are grooved to provide minimal installation time. The valve package includes the system (manual) shut-off Control Valve, auto-matic water Control valve, and water-flow/supervisory switches. When dry pilot actuation is utilized, a built-in air compressor with associated controls provides an automatic air supply for the dry pilot lines.

Integral to the DV-5 Red-E Cabinet is a control panel and back-up batteries for providing electrical alarm, supervisory, and trouble functions. All switches within the cabinet are pre-wired to the control panel, making the electrical connections for power, detection cir-cuits (as applicable), and alarms the only remaining connections to com-plete the system.

In addition to the control panel being integral to the DV-5 Red-E Cabinet, windows have been provided in the door for viewing the releasing panel functions and essential system pres-sure gauges. A lock for the control panel access door is standard, and a lock for the cabinet door is optional.

Features and benefits are as follows:

•aesthetically pleasing appearance
•professionally assembled
•internally wired
•custom manufactured
•all gauges and panel display are externally visible
•removable side panels for ease of maintenance
•furniture grade rollers (4) are standard at bottom of cabinet

The DV-5 Red-E Cabinet has been designed to readily incorporate 1-1/2 thru 8 inch (DN40 thru DN200) valve risers for the following types of deluge systems:

•Electric Actuation
•Dry Pilot Actuation
•Wet Pilot Actuation


What makes it special?

Easy to Install
//Entire package is pre-wired
//Water inlet and outlets to the valve riser are grooved to ensure minimal installation time
//Completely pre-trimmed valve inside
//Easy to move - lift point eye bolts
//Tested and fully functional

Weather Proof
//Available with optional heated housing
//Applicable for indoor OR outdoor use
//Comes complete with water resistant seal to project the entire contents of the cabinet
Pre-tested
//Tyco's cabinet system provides you with one complete solution with no need for any additional testing. The valves and components are all pre-tested by our Tyco engineers

European Made
//Uses the famous DV-5 which is produced in Spain
Designed, engineered and built at our Centre of Excellence for valve engineering in the Netherlands

   
Options: Deluge Wet Deluge Dry Deluge Electric
  Actuation Actuation Actuation
       
       
Heater YES YES
Light and socket plug 230VAC YES YES YES
Water motor alarm WMA-1 YES YES YES
Low temperature switch YES YES YES
Manual pull station accessible from the outside YES YES YES
Without downstream butterfly valve YES YES YES
Cabinet colour grey RAL7035 YES YES YES
Potter Release Panel YES YES YES
Handbook YES YES YES
Factory acceptance test YES YES YES
Split flanges (adapter grooved to flanged) YES YES YES


 
  Description Model Data Sheet UL C-UL/ULC FM  
               
  System Shut-Off Valve, 1-1/2"-2" (DN40-DN50) BBVSCS02   X(4) X(4) X(4)  
  System Shut-Off Valve, 3"-8" (DN80-DN200) BFV-N TFP1510 X X X  
               
  Automatic Water Control Valve DV-5 TFP1305 X X X  
               
  Actuation Trim            
               
  Electric   TFP1320 X X X  
               
  Dry Pilot   TFP1315 X X X  
               
  Wet Pilot   TFP1310 X X X  
               
  Pressure Alarm Switch PS10-2A   X(5) X(5) X(5)  
  Pressure Alarm Switch PS40-2A   X(5) X(5) X(5)  
  Control Panel(1) PFC-4410RC   X(5) X(5) X(5)  
  Air Maintenance Device(2), Regulator Type AMD-1 TFP1221 X X X  
  Air Maintenance Device(3), Switch Type AMD-2 TFP1231 X X X  
  Nitrogen Maintenance Device(3) AMD-3 TFP1241 X X X  
 
Notes:
 
1. The Model AMD-1 Air Maintenance Device, in addition to an Auxiliary Air Tank, is utilized as standard equipment for Dry Pilot Actuation. In the case of Dry Pilot Actuation, the automatic air supply is utilized for the air pressure required for the dry pilot lines. An OL12516AC (1/6 HP) Air Compressor is provided as standard for maintaining the air pressure in the Auxiliary Air Tank. The Model PFC-4410RC is standard. The Red-E Cabinet may be ordered without an integral control panel.
 
2. The Model AMD-1 Air Maintenance Device, in addition to an Auxiliary Air Tank, is utilized as standard equipment for Dry Pilot Actuation. In the case of Dry Pilot Actuation, the automatic air supply is utilized for the air pressure required for the dry pilot lines. An OL12516AC (1/6 HP) Air Compressor is provided as standard for maintaining the air pressure in the Auxiliary Air Tank.
 
3. The Model AMD-2 Air Maintenance Device and Model AMD-3 Nitrogen Maintenance Device, as well as the Model AMD-1 Air Maintenance Device, are offered as options when the Red-E Cabinet for Dry Pilot Actuation is ordered without a built-in automatic air supply (i.e., air compressor).
 
4. Approvals under the name of Potter Electric Signal Company 5. Approvals under the name of Potter Electric Signal Company
 

Contact us if you need more details on Fire Protection Package. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Deluge Fire Protection Package、Cabinet Integrated Deluge Fire Protection Packag. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Control > Control Fire